Sign up to receive a text message or email when new bids are added!
Bid Title: RFP - Water Restoration Plant Pump and Motor Rebuild
Category: Other Professional Services & Non Design Consultants
Status: Open
Bid Recipient: City of Grants Pass Administration - City Recorder

Description:
The City of Grants Pass, Oregon, is requesting quotes to rebuild two immersible sewage pumps and motors to remanufactured condition.

Pump One, a 16 X 16 model I16K-MD-IEUC6, Wemco Hidrostal screw centrifugal pump. 
Material: cast iron with high chrome iron liner and stainless-steel impeller. 
Conditions: 11100/10700/12000/2000 GPM.
Against: 38’/41’/30’/30’ TDH.
At: 1140/1140/1140/660 RPM.
CW rotation viewed from the top of the motor. Vertical dry-pit pump support base sole plate and 20” X 16” suction box with clean out.

Motor One, an immersible motor, 150 HP, 1186 RPM, IEUC6 frame, explosion proof enclosure, internal moisture probe, oil bath tandem mechanical seals, 3 phase, 60 HZ, 460-volt, motor service factor 1.10 with 32’ of power and control leads, bearing temperature sensor and float switch, 120-volt moisture detector relay. 

Pump Two, a 10 X 5, model H5K-MH-HEUC4, Wemco Hidrostal screw centrifugal pump.
Material: cast iron with high chrome iron liner and stainless-steel impeller. 
Conditions: 1460/2400/1050/400 GPM.
Against: 185’/115’/325’/70’ TDH.
At: 1750/1750/1750/900 RPM.
CW rotation viewed from the top of the motor. Vertical dry-pit pump support base sole plate and 10” suction elbow with clean out.

Motor Two, an immersible motor, 110 HP, 1780 RPM, HEUC4 frame, explosion proof enclosure, internal moisture probe, oil bath tandem mechanical seals, 3 phase, 60 HZ, 460-volt, motor service factor 1.10 with 40’ of power and control leads, bearing temperature sensor and float switch, 120-volt moisture detector relay. 

Pump One is located at the City’s Water Restoration Plant, 1200 SW Greenwood Ave, Grants Pass, OR 97526.

Pump Two is located at the City’s Darneille Pump Station, 3100 South river Rd, Grants Pass, OR 97527.

Quotes are to be submitted on proposal form included within the Scope of Work in a sealed envelope.
Proposer is to include with quote a list of Wemco Hidrostal screw centrifugal pumps rebuilt within the last 5 years.  The list is to include size of pump, pump application and pump owner reference contact information. The length of list is to be sufficient to demonstrate rebuild expertise.

Evaluation Criteria: Proposals shall be reviewed and evaluated based upon cost, experience and references.
Publication Date/Time:
2/6/2019 9:30 AM
Closing Date/Time:
Open Until Contracted
Submittal Information:
Submittal deadline is Friday, March 1, 2019 before 3:00 p.m. local time
Contact Person:
For additional information please contact Gary Brelinski, Water Restoration Plant Superintendent, at 541-450-6122 or Kevin Smith, Water Restoration Plant Specialist, at 541-450-6124.

Miscellaneous:
The proposal submittals should be labeled and directed to:

City of Grants Pass WRP Pump and Motor Rebuild Project
Attn: Karen Frerk, City Recorder
101 NW A Street
Grants Pass, Oregon 97526

Related Documents:

Return To Main Bid Postings Page